Inspection & Maintenance
4.7 Maintaining the main contact system
3WJ Air Circuit breakers
190 Operating Instructions, 12/2022, L1V30828903001-01
For 3200 A/4000 A versions
1. Insert the conduction paths into the rear housing.
2. Fix the conduction paths to the housing by means of the corresponding screws and
washers.
Installing the contact carriers
For 2000 A/2500 A versions: insert the spacer into the rear housing.
Insert the coupling bolts into the contact carriers.
Insert the contact carriers into the rear housing and secure with the corresponding screws
and washers.
Rotate the contact carriers upwards.