Description
2.2 Electronic components
3WJ Air Circuit breakers
Operating Instructions, 12/2022, L1V30828903001-01
47
G tripping operation
Due to the activation limits of 150 A (FSI) and 200 A (FSII), a ground fault response value of
100 A cannot be ensured with a one-phase load. In this case, the minimum response value is
I
g = 300 A.