2.2 Electronic components
3WJ Air Circuit breakers
Operating Instructions, 12/2022, L1V30828903001-01
49
Protection function has tripped (overcurrent)
Indicator lights up when the "QUERY" button is
pressed
Only one reason for tripping is displayed
Only the last reason for tripping is displayed
T.U. ERROR LED
1st T.U. Error flashes:
The protection function is restricted; the protection
parameters are reset to the minimum values.
Cause:
Electronic trip unit defective
2nd T.U. Error lights up continuously:
The protection function is not ensured.
Cause:
Electronic trip unit defective