Accessories
3.2 Preparatory and concluding installation steps for the installation of internal accessories
3WJ Air Circuit breakers
58 Operating Instructions, 12/2022, L1V30828903001-01
Opening the circuit breaker and discharging the stored-energy spring
1. Check that the circuit breaker is ready to close ("OK" indication) and the stored-energy spring
is charged ("CHARGED" indication).
2. Press the CLOSE button.
3. Check that the "CLOSED" and "DISCHARGED" indications are active.
4. Press the OPEN button.
5. Check that the "OPEN" indication is active.
Operator panel
Removal
Check that the Circuit Breaker is OPEN and the stored-energy spring is discharged
Remove the secondary disconnect terminals
Unscrew the operator panel
Pull the spring-charging lever down
Remove the operator panel