3.7 Accessories for the Electronic Trip Unit
3WJ Air Circuit breakers
Operating Instructions, 12/2022, L1V30828903001-01
87
Article No.
Description
Article No.
Manual function tester for electronic trip unit
3WL9111-0AT32-0AA0
View
LED for indicating the operating voltage
Control keys
6 LEDs for indicating the test results
Preparatory work
Open and disconnect the Circuit Breaker.
Note the setting values of the electronic trip unit.
Deactivate ground fault protection (if available) on the electronic trip unit (I
g = OFF).
Setting value I
R = 1.0 In
Remove the cover cap from test socket X25 on the ETU.
CAUTION
Equipment damage
If the hand-held test device is used while the Circuit Breaker is closed, this can cause false
tripping and destroy the hand-held test device.