If the time constant is inadequate, the setting of 'b1.TIM' can be
changed manually. Set the time constant in a range from '1' to '400'.
In this case:
Setting '1' indicates a very weak attenuation.
Setting '400' indicates a strong attenuation.
The currently determined deviation is displayed in Diagnostics val‐
ue '15.DEVI - Dynamic control valve behavior' (Page 220). The
positioner triggers a message if the current value exceeds one of
the three parameterizable thresholds.
Factory setting: Auto
b2.LIMIT - Limit
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set a base limit in percent. The base limit
defines the magnitude of the permissible deviation from the expec‐
ted position course. The limit serves as a reference variable for the
fault message factors.
Set the base limit in a range from '0.1' to '100.0'.
Factory setting: 1.0
b3.FACT1 - Factor 1
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'b2.LIMIT' and 'b3.FACT1'.
The threshold 1 message is displayed when threshold 1 is excee‐
ded. This message is only output if threshold 2 or 3 is not exceeded
at the same time. The process to activate and display this message
is described in the 'XDIAG' parameter.
Factory setting: 5.0
b4.FACT2 - Factor 2
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'b2.LIMIT' and 'b4.FACT2'.
The threshold 2 message is displayed when threshold 2 is excee‐
ded. This message is only output if threshold 3 is not exceeded at
the same time. The process to activate and display this message is
described in the 'XDIAG' parameter.
Factory setting: 10.0
Parameter assignment
8.4 Description of parameters
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE 169

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 6DR52 Series and is the answer not in the manual?

Siemens SIPART PS2 6DR52 Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 6DR52 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals