59 mA Setpoint current 0.0 ... 20.0 mA â‘¡
60 PZ Supply pressure (PZ) 99.999 (bar)
999.99 (psi)
9.9999 (MPa)
- â‘¢
63 PZMAX Supply pressure (PZ) min/max pointer - â‘ 
64 N_MIN Event counter 0 ... 99999 - â‘ 
11.2.4 Meaning of the diagnostics values
11.2.4.1 Diagnostic value '1.STRKS - Number of total strokes'
Display range: 0 ... 4.29E9
Purpose: In operation, the movements of the actuator are summed up and
displayed in this diagnostics parameter as the number of strokes.
Unit: 100% strokes, i.e. the path between 0% and 100% and back.
11.2.4.2 Diagnostic value '2.CHDIR - Number of changes in direction'
Display range: 0 ... 4.29E9
Purpose: Every change in direction of the actuator is noted in the controller
and added to the number of changes in direction.
11.2.4.3 Diagnostic value '3.\\CNT - Number of fault messages'
Display range: 0 ... 4.29E9
Purpose: Every fault is noted in the closed-loop controller with '3. CNT' and
added to the number of fault messages.
11.2.4.4 Diagnostic value '4.A1CNT - Number of alarms 1' / '5.A2CNT - Number of alarms 2'
Requirement: '44.AFCT' Alarm function (Page 156) parameter is activated.
Display range: 0 ... 4.29E9
Purpose: This value indicates how often the alarm has been triggered.
Diagnostics and troubleshooting
11.2 Diagnostics
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE 215

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 6DR52 Series and is the answer not in the manual?

Siemens SIPART PS2 6DR52 Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 6DR52 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals