2.5 Distance Protection
167
7SD5 Manual
C53000-G1176-C169-1
Tripping Logic The output signals generated by the individual zones are logically connected to the
output signals „Dis.Gen. Trip“, „Dis.Trip 1pL1“, „Dis.Trip 1pL2“,
„Dis.Trip 1pL3“, „Dis.Trip 3p“ in the actual tripping logic. The single-pole in-
formation implies that tripping will take place single-pole only. Furthermore, the zone
that initiated the tripping is identified; if single-pole tripping is possible, this is also
alarmed, as shown in the zone logic diagrams (Figures 2-55 up to 2-59). The actual
generation of the commands for the tripping (output) relay is executed within the trip-
ping logic of the entire device.
2.5.4.2 Setting Notes
The trip delay times of the distance stages and intervention options which are also pro-
cessed in the tripping logic of the distance protection were already considered with the
zone settings.
Further setting options which affect the tripping are described as part of the tripping
logic of the device.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals