EasyManua.ls Logo

Siemens siprotec 7SD5

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.22 Monitoring Function
569
7SD5 Manual
C53000-G1176-C169-1
4.22 Monitoring Function
Measured Values
Current sum I
F
= | I
L1
+ I
L2
+ I
L3
+ k
I
· I
E
| >
SUM.I Threshold · I
N
+ SUM.FactorI ·Σ | I |
- SUM.ILimit for I
N
= 1 A 0.10 A to 2.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 10.00 A Increments 0.01 A
- SUM.FACTOR I 0.00 to 0.95 Increments 0.01
Voltage sum U
F
= | U
L1
+ U
L2
+ U
L3
+ k
U
· U
EN
| > 25 V
Current Symmetry | I
min
|/| I
max
| < BAL.FACTOR.I
as long as I
max
/I
N
> BAL.ILIMIT/I
N
- BAL.FACTOR.I 0.10 to 0.95 Increments 0.01
- BAL.ILIMIT for I
N
= 1 A 0.10 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 5.00 A Increments 0.01 A
- T BAL.ILIMIT 5 s to 100 s Increments 1 s
Broken conductor One conductor without current, the others with current
(monitoring of current transformer circuits on current step
change in one phase without residual current)
Voltage Symmetry | U
min
|/| U
max
| < BAL.FACTOR.U
as long as | U
max
| > BAL.ULIMIT
- BAL.FACTOR.U 0.58 to 0.95 Increments 0.01
- BAL.ULIMIT 10 V to 100 V Increments 1 V
- T BAL.ULIMIT 5 s to 100 s Increments 1 s
Voltage phase sequence U
L1
before U
L2
before U
L3
as long as | U
L1
|, | U
L2
| , | U
L3
| > 40 V/3
Non-symmetrical voltages
(Fuse failure monitoring)
3 · U
0
> FFM U> OR 3 · U
2
> FFM U>
AND at the same time
3 · I
0
< FFM I< AND 3 · I
2
< FFM I<
- FFM U> 10 V to 100 V Increments 1 V
- FFM I<for I
N
= 1 A 0.10 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 5.00 A Increments 0.01 A
Three-phase measuring voltage failure
(fuse failure monitoring)
All U
Ph-E
< FFM UMEAS <
AND at the same time
all I
Ph
< FFM I
delta
AND
All I
Ph
> (I
Ph
> (Dist.))
OR
All U
Ph-E
< FFM UMEAS <
AND at the same time
All I
Ph
< (I
Ph
> (Dist.))
AND
All I
Ph
> 40 mA
- FFM UMEAS < 2 V to 100 V Increments 1 V
- FFM I
delta
for I
N
= 1 A 0.05 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.25 A to 5.00 A Increments 0.01 A
- T U-Monitoring (wait time for additional measured
voltage failure monitoring)
0.00 s to 30.00 s Increments 0.01 s
- T UT mcb 0 ms to 30 ms Increments 1 ms
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Related product manuals