EasyManuals Logo

Siemens siprotec 7SD5 User Manual

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #350 background imageLoading...
Page #350 background image
2 Functions
350
7SD5 Manual
C53000-G1176-C169-1
The double-ended fault locating method used here has the following advantages over
the single-ended method:
• Correct fault locating is possible even with power flowing in the line, with double-
sided infeed and high fault resistances.
• The precision of fault locating is not affected by an inaccurate setting of the earth
impedance compensation.
• The method is stable against the influence of a parallel line, so parallel line compen-
sation is not required.
• The accuracy can be increased if the line asymmetry (selection of the central con-
ductor) is taken into account.
Output of the Fault
Locator
The fault locating issues the following results:
• The short-circuit loop which was used to determine the fault reactance,
• The reactance X in Ω primary and Ω secondary,
• The resistance R in Ω primary and Ω secondary,
• The distance to fault d in kilometers or miles of the line proportional to the reac-
tance, converted on the basis of the set line reactance per unit line length,
• The distance to fault d in % of the line length, calculated on the basis of the set re-
actance per unit length and the set line length.
The additional indications always show the results of single-ended fault locating.
• Where double-ended fault locating is configured, the results of single-ended fault
locating are output in any case in additional indications
– „Rpri single. =“ (No.1135),
– „Xpri single. =“ (No.1136),
– „Rsec single. =“ (No.1137) and
– „Xsec single. =“ (No.1138)
• If the double-ended fault locator fails, they are output as „main results“ in the indi-
cations
– „Rpri =“ (No.1114),
– „Xpri =“ (No.1115),
– „Rsec =“ (No.1117) and
– „Xsec =“ (No.1118)
.
The fault location indicated in per cent can, at the same time, be output as BCD-code
(Binary Coded Decimal). This, however, must have been preset in address 138 during
the configuration of the protection functions (Section 2.1.1.3). A further prerequisite is
that the required number of binary outputs is allocated for this purpose.
10 output relays are needed. They are classified as follows:
• 4 outputs for the units (1·2
0
+ 1·2
1
+ 1·2
2
+ 1·2
3
),
• 4 outputs for the tens (10·2
0
+ 10·2
1
+ 10·2
2
+ 10·2
3
),
• 1 output for the hundreds (100·2
0
),
• 1 output for the ready-state annunciation „BCD dist. VALID“ (No. 1152).
Once a fault was located, the corresponding binary outputs pick up. Then the output
„BCD dist. VALID“ signals that the data are now valid. The duration can be se-
lected. In the event of a new fault, the data of the former fault are cleared automatically.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals