EasyManua.ls Logo

Siemens siprotec 7SD5

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Functions
384
7SD5 Manual
C53000-G1176-C169-1
Figure 2-166 Logic diagram of the fuse failure monitor with zero and negative sequence system
Three-Phase Mea-
suring Voltage
Failure "Fuse
Fail ure Monit o r"
A three-phase failure of the secondary measured voltage can be distinguished from
an actual system fault by the fact that the currents have no significant change in the
event of a failure in the secondary measured voltage. For this reason, the sampled
current values are routed to a buffer, so that the difference between the present and
stored current values can be analysed to recognize the magnitude of the current dif-
ferential (current differential criterion). A three-pole voltage failure is detected if
All three phase-to-earth voltages are smaller than the threshold FFM U<max
(3ph),
The current differential in all three phases is smaller than the threshold FFM
Idelta (3p).
All three phase current amplitudes are greater than the minimum current Iph> for
impedance measurement by the distance protection.
If no stored current values are present (yet), the current magnitude criterion is resorted
to. A three-pole system voltage failure is detected in this case if
All three phase-to-earth voltages are smaller than the threshold FFM U<max
(3ph),
All three phase current amplitudes are smaller than the minimum current Iph> for
impedance measurement by the distance protection, and
All three phase current amplitudes are greater than a fixed set noise threshold
(40mA).
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Related product manuals