4 Technical Data
532
7SD5 Manual
C53000-G1176-C169-1
Supported network interfaces G703.1 with 64 kbit/s;
X.21 with 64 or 128 or 512 kbit/s
S0 (ISDN) with 64 Kbits or 128 Kbits/s
Pilot wires with 128 Kbits/s;
Connection to communication converter See table above under module FO 5
Transmission rate 64 kbit/s with G703.1
512 kbit/s or 128 kBit/s or 64 kbit/s with X.21
64 Kbits/s or 128 Kbits/s with S0 (ISDN)
64 Kbits/s or 128 kBit/s with pilot wires
Max. runtime time 0.1 ms to 30 ms Increments 0.1 ms
Max. runtime difference 0.000 ms to 3.000 ms Increments 0.001 ms
Transmission accuracy CRC 32 according to CCITT or ITU