4.14 Time Overcurrent Protection
557
7SD5 Manual
C53000-G1176-C169-1
Further Definite Stage
Time factors D
IP
(phas-
es)
0.50 s to 15.00 s
or ∞ (ineffective)
Increments 0.01 s
D
3I0P
(earth)
0.50 s to 15.00 s
or ∞ (ineffective)
Increments 0.01 s
Additional time delays T
IP delayed
(phases)
0.00 s to 30.00 s Increments 0.01 s
T
3I0P delayed
(earth)
0.00 s to 30.00 s Increments 0.01 s
Characteristics See Figure 4-2 and 4-3
Tolerances currents Pickup values at 1.05 ≤ I/I
P
≤ 1.15
or 1.05 ≤ I/3I
0P
≤ 1.15
Tolerances times 5 % ± 15 ms for 2 ≤ I/I
P
≤ 20 and D
IP
/s ≥ 1
or 2 ≤ I/3I
0P
≤ 20 and D
3I0P
/s ≥ 1
Defined times 1 % of setting value or 10 ms
Pickup value I
Ph
>>> (phases) for I
N
= 1 A 0.10 A to 25.00 A
or ∞ (ineffective)
Increments 0.01 A
for I
N
= 5 A 0.50 A to 125.00 A
or ∞ (ineffective)
Pickup value 3I
0
>>> (earth) for I
N
= 1 A 0.05 A to 25.00 A
or ∞ (ineffective)
Increments 0.01 A
for I
N
= 5 A 0.25 A to 125.00 A
or ∞ (ineffective)
Delays T
IPh
>>> 0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
T
3I0
>>> 0.00 s to 30.00 s
or ∞ (ineffective)
Increments 0.01 s
Dropout to pickup ratio Approx. 0.95 for I/I
N
≥ 0.5
Pickup times (fast relays/high-speed relays) approx. 30/25 ms
Dropout times Approx. 30 ms
Tolerances currents Currents 3 % of setting value or 1 % nominal current
Times 1 % of setting value or 10 ms
The set times are pure delay times.