1 Introduction
26
7UT613/63x Manual
C53000-G1176-C160-2
Thermal Overload
Protection
Thermal replica of current-initiated heat losses
True RMS current calculation
Can be assigned to any desired side of the protective object
Adjustable thermal warning stage
Adjustable current warning stage
With or without including the ambient or coolant temperature (by means of external
resistance temperature detector via RTD-box)
Alternative evaluation of the hot-spot temperature according to IEC 60354 with cal-
culation of the reserve power and ageing rate (by means of external resistance tem-
perature detector via RTD-box)
2 breaker failure protection functions possible
Overexcitation Pro-
tection (device with
voltage measure-
ment inputs)
Processing of the voltage/frequency ration U/f, which represents the induction B of
a shunt reactance (transformer, shunt reactor)
Adjustable warning and tripping stage (with independent delay time)
Inverse standard characteristic or user-defined trip characteristic for calculation of
the thermal stress, selectable
Reverse Power Pro-
tection (Device with
Voltage Measure-
ment Inputs)
Real power calculation from positive sequence components
Short operating time or exact calculation of the active power via 16 cycles
Exact real power calculation for small power factor by compensating the error angle
of the measuring locations
Insensitive to power fluctuations
Short-time stage with external criteria, e.g. with closed emergency tripping
Forward Power
Monitoring (devic-
es with measuring
voltage inputs)
Real power calculation from positive sequence components
Supervision of overvoltage (P>) or undervoltage (P<) of power with individually ad-
justable power limits
Short operating time or exact calculation of the active power via 16 cycles
Automatic blocking of stage P< for recognised measured voltage failure or wire
break in CT secondary circuit
Undervoltage Pro-
tection (Device with
Voltage Measure-
ment Inputs)
Two-stage three-phase undervoltage measurement
Evaluation of positive sequence component of the connected voltages, therefore in-
dependent of asymmetries
Automatic blocking for measuring voltage failure
Adjustable dropout ratio
Overvoltage Pro-
tection (Device with
Voltage Measure-
ment Inputs)
Two-stage three-phase overvoltage measurement
Evaluation of the largest of the three phase-to-ground voltages or the largest of the
three phase-to-phase voltages (largest of the three phase-to-phase voltages (can
be set)
Adjustable dropout ratio