EasyManuals Logo

Siemens SIPROTEC User Manual

Siemens SIPROTEC
776 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #238 background imageLoading...
Page #238 background image
Functions
2.8 Earth Fault Protection in Earthed Systems (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
238
During the selection of the current and time settings, regard must be taken as to whether a stage should be
direction dependent and whether it uses teleprotection. Refer also to the margin headings „Determination of
Direction“ and „Teleprotection with Earth Fault Protection“.
Figure 2-115 Curve parameters in the logarithmic–inverse characteristic
Zero-Sequence Voltage-controlled Stage with Inverse Characteristic
If you have configured the zero-sequence voltage controlled stage (address 131 Earth Fault O/C = U0
inverse), you set the operating mode first: Address 3140 Op. mode 3I0p. This stage can be set to operate
Forward (usually towards line) or Reverse (usually towards busbar) or Non-Directional (in both direc-
tions). If the stage is not required, set its mode to Inactive.
Address 3141 3I0p PICKUP indicates the minimum current value above which this stage is required to oper-
ate. The value must be exceeded by the minimum earth fault current value.
The voltage-controlled characteristic is based on the following formula:
U
0
is the actual zero-sequence voltage. U
0 min
is the setting value U0inv. minimum (address 3183). Please
take into consideration that the formula is based on the zero-sequence voltage U
0
, not on 3U
0
. The function is
illustrated in the Technical Data.
Figure 2-116 shows the most important parameters. U0inv. minimum displaces the voltage-controlled char-
acteristic in direction of 3U
0
. The set value is the asymptote for this characteristic (t → ∞). In Figure 2-116, a'
shows an asymptote that belongs to the characteristic a.
The minimum voltage 3U0>(U0 inv) (address 3182) is the lower voltage threshold. It corresponds to the line
c in Figure 2-116. In characteristic b (asymptote not drawn) the curve is cut by the minimum voltage 3U0>(U0
inv) (line c).
In address 3184, an additional time T forw. (U0inv) that is added to the voltage-controlled characteristic
can be set for directional-controlled tripping.
With the non-directional time T rev. (U0inv) (address 3185) a non-directional back-up stage can be gen-
erated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC and is the answer not in the manual?

Siemens SIPROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC
CategoryProtection Device
LanguageEnglish

Related product manuals