Technical Data
4.24 Monitoring Functions
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
628
4.24 Monitoring Functions
Measured values
Trip circuit monitoring
Current sum I
F
= | I
L1
+ I
L2
+ I
L3
+ k
I
· I
E
| >
SUM.I THRESHOLD · I
N
+ SUM.I FACTOR ·Σ | I |
- SUM.ITHRESHOLD for I
N
= 1 A 0.10 A to 2.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 10.00 A Increments 0.01 A
- SUM.I FACTOR 0.00 to 0.95 Increments 0.01
Voltage sum U
F
= | U
L1
+ U
L2
+ U
L3
+ k
U
· U
EN
| > 25 V
Current symmetry | I
min
|/| I
max
| < BAL.FACTORI
while I
max
/I
N
> BAL.ILIMIT/I
N
- BAL. FACTORI 0.10 to 0.95 Increments 0.01
- BAL.ILIMIT for I
N
= 1 A 0.10 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 5.00 A Increments 0.01 A
- T BAL.ILIMIT 5 s to 100 s Increments 1 s
Broken conductor monitoring of the current transformer circuits on current step
change without voltage step change
Voltage symmetry | U
min
|/| U
max
| < BAL.FACTORU
while | U
max
| > BAL.ULIMIT
- BAL.FACTORU 0.58 to 0.95 Increments 0.01
- BAL.ULIMIT 10 V to 100 V Increments 1 V
- T BAL.ULIMIT 5 s to 100 s Increments 1 s
Voltage phase sequence U
L1
before U
L2
before U
L3
while | U
L1
|, | U
L2
| , | U
L3
| > 40 V/3
Asymmetrical measuring voltage failure
(Fuse Failure Monitor)
3 · U
0
> FFM U> OR 3 · U
2
> FFM U>
AND simultaneously
3 · I
0
< FFM I< AND 3 · I
2
< FFM I<
- FFM U> 10 V to 100 V Increments 1 V
- FFM I<for I
N
= 1 A 0.10 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.50 A to 5.00 A Increments 0.01 A
Three-phase measuring voltage failure
(Fuse Failure Monitor)
all U
Ph-E
< FFM UMEAS <
AND simultaneously
all ΔI
Ph
< FFM I
delta
- FFM UMEAS < 2 V to 100 V Increments 1 V
- FFM I
delta
for I
N
= 1 A 0.05 A to 1.00 A Increments 0.01 A
for I
N
= 5 A 0.25 A to 5.00 A Increments 0.01 A
- T V SUPERVISION (waiting time for additional mea-
sured voltage failure monitoring)
0.00 s to 30.00 s Increments 0.01 s
- T mcb 0 ms to 30 ms Increments 1 ms
Phase angle positive-sequence power Message when the angle is located inside the area of the P-Q
level parameterised by ϕA and ϕB.
- ϕA, ϕB 0° to 259° Increment 1°
- I1 for I
N
= 1 A 0.05 A to 2.00 A Increment 0.01 A
for I
N
= 5 A 0.25 A to 10.00 A Increment 0.01 A
- U1 2 V to 70 V Increment 1 V
Response time Approx. 30 ms