EasyManuals Logo

Siemens SIPROTEC User Manual

Siemens SIPROTEC
776 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #182 background imageLoading...
Page #182 background image
Functions
2.6 Power Swing Detection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
182
2.6.2 Method of Operation
To detect a power swing, the rate of change of the impedance vectors is measured.
Figure 2-77 Impedance vectors during a power swing and during a fault
To ensure stable and secure operation of the power swing detection without the risk of an overfunction of the
power swing detection during a fault, the following measuring criteria are used:
• Trajectory monotony:
During a power swing, the measured impedance features a directional course of movement. This course of
movement occurs exactly when not more than one of the two components ΔR and ΔX features a change of
direction within one measuring window. A fault usually causes a change of direction in ΔR as well as in ΔX
within one measuring window.
• Trajectory continuity:
During a power swing, the distance between two subsequent impedance values features a clear change in
ΔR or ΔX. In case of a fault, the impedance vector jumps to the fault impedance without moving afterwards.
• Trajectory uniformity
During a power swing, the ratio between two subsequent changes of ΔR or ΔX will not exceed a threshold.
A fault usually causes an abrupt jump of the impedance vector from the load impedance to the fault imped-
ance.
The indication of a power swing is triggered when the impedance vector enters the power swing measuring
range PPOL (refer to Figure 2-78) and the criteria of power swing detection are met. The fault detection range
APOL for the polygonal characteristic is made up of the largest quantitative values set for R and X of all active
zones. The power swing area has a minimum distance Z
Diff
of 5 Ω (at I
N
= 1 A) or 1 Ω (at I
N
= 5 A) in all direc-
tions from the fault detection zone. Analog features apply for the MHO characteristics. The power swing circle
also has a distance of 5 Ω (at II
N
= 1 A) or 1 Ω (at II
N
= 5 A) from the largest zone circle. The power swing mea-
suring range has no load trapezoid cutout.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC and is the answer not in the manual?

Siemens SIPROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC
CategoryProtection Device
LanguageEnglish

Related product manuals