Functions
2.17 Automatic Reclosure Function (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
341
For the 3rd cycle:
For the 4th cycle:
5th to 8th Reclose Cycle
If more than four cycles were set during configuration of the functional scope, the dead times preceding the fifth
(5th) through the ninth (9th) reclosing attempts are equal to the open circuit breaker time which precedes the
fourth (4th) reclosing attempt.
3472 3.AR: START Start in 3rd cycle generally allowed
3473 3.AR: T-ACTION Action time for the 3rd cycle
3475 3.AR Tdead 1Flt Dead time after 1-phase pickup
3476 3.AR Tdead 2Flt Dead time after 2-phase pickup
3477 3.AR Tdead 3Flt Dead time after 3-phase pickup
3478 3.AR Tdead1Trip Dead time after 1-pole tripping
3479 3.AR Tdead3Trip Dead time after 3-pole tripping
3480 3.AR: Tdead EV. Dead time after evolving fault
3481 3.AR: CB? CLOSE CB ready interrogation before reclosing
3482 3.AR SynRequest Sync. check after 3-pole tripping
3483 4.AR: START Start in 4th cycle generally allowed
3484 4.AR: T-ACTION Action time for the 4th cycle
3486 4.AR Tdead 1Flt Dead time after 1-phase pickup
3487 4.AR Tdead 2Flt Dead time after 2-phase pickup
3488 4.AR Tdead 3Flt Dead time after 3-phase pickup
3489 4.AR Tdead1Trip Dead time after 1-pole tripping
3490 4.AR Tdead3Trip Dead time after 3-pole tripping
3491 4.AR: Tdead EV. Dead time after evolving fault
3492 4.AR: CB? CLOSE CB ready interrogation before reclosing
3493 4.AR SynRequest Sync. check after 3-pole tripping