Appendix
A.8 Information List
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
719
1511 Thermal Overload Protection
OFF (Th.Overload OFF)
Therm. Overload OUT on
off
* * LED BO 167 11 1 Yes
1512 Thermal Overload Protection
BLOCKED (Th.Overload BLK)
Therm. Overload OUT on
off
on off * LED BO 167 12 1 Yes
1513 Thermal Overload Protection
ACTIVE (Th.O/L ACTIVE)
Therm. Overload OUT on
off
* * LED BO 167 13 1 Yes
1515 Th. Overload: Current Alarm (I
alarm) (Th.O/L I Alarm)
Therm. Overload OUT on
off
* * LED BO 167 15 1 Yes
1516 Th. Overload Alarm: Near
Thermal Trip (Th.O/L Θ Alarm)
Therm. Overload OUT on
off
* * LED BO 167 16 1 Yes
1517 Th. Overload Pickup before trip
(Th.O/L Pickup)
Therm. Overload OUT on
off
* * LED BO 167 17 1 Yes
1521 Th. Overload TRIP command
(Th.O/L TRIP)
Therm. Overload OUT * on * LED BO 167 21 2 Yes
2054 Emergency mode (Emer. mode) Device OUT on
off
on off * LED BO 192 37 1 Yes
2701 >AR: Switch on auto-reclose
function (>AR on)
Auto Reclose SP * * * LED BI BO 40 1 1 Yes
2702 >AR: Switch off auto-reclose
function (>AR off)
Auto Reclose SP * * * LED BI BO 40 2 1 Yes
2703 >AR: Block auto-reclose function
(>AR block)
Auto Reclose SP on
off
* * LED BI BO 40 3 1 Yes
2711 >External start of internal Auto
reclose (>AR Start)
Auto Reclose SP * on * LED BI BO 40 11 2 Yes
2712 >AR: External trip L1 for AR start
(>Trip L1 AR)
Auto Reclose SP * on * LED BI BO 40 12 2 Yes
2713 >AR: External trip L2 for AR start
(>Trip L2 AR)
Auto Reclose SP * on * LED BI BO 40 13 2 Yes
2714 >AR: External trip L3 for AR start
(>Trip L3 AR)
Auto Reclose SP * on * LED BI BO 40 14 2 Yes
2715 >AR: External 1pole trip for AR
start (>Trip 1pole AR)
Auto Reclose SP * on * LED BI BO 40 15 2 Yes
2716 >AR: External 3pole trip for AR
start (>Trip 3pole AR)
Auto Reclose SP * on * LED BI BO 40 16 2 Yes
2727 >AR: Remote Close signal (>AR
RemoteClose)
Auto Reclose SP * on * LED BI BO 40 22 2 Yes
2731 >AR: Sync. release from ext.
sync.-check (>Sync.release)
Auto Reclose SP * * * LED BI BO 40 31 2 Yes
2737 >AR: Block 1pole AR-cycle
(>BLOCK 1pole AR)
Auto Reclose SP on
off
**LEDBIBO40321Yes
2738 >AR: Block 3pole AR-cycle
(>BLOCK 3pole AR)
Auto Reclose SP on
off
**LEDBIBO40331Yes
2739 >AR: Block 1phase-fault AR-
cycle (>BLK 1phase AR)
Auto Reclose SP on
off
**LEDBIBO40341Yes
2740 >AR: Block 2phase-fault AR-
cycle (>BLK 2phase AR)
Auto Reclose SP on
off
**LEDBIBO40351Yes
2741 >AR: Block 3phase-fault AR-
cycle (>BLK 3phase AR)
Auto Reclose SP on
off
**LEDBIBO40361Yes
2742 >AR: Block 1st AR-cycle (>BLK
1.AR-cycle)
Auto Reclose SP on
off
**LEDBIBO40371Yes
2743 >AR: Block 2nd AR-cycle (>BLK
2.AR-cycle)
Auto Reclose SP on
off
**LEDBIBO40381Yes
2744 >AR: Block 3rd AR-cycle (>BLK
3.AR-cycle)
Auto Reclose SP on
off
**LEDBIBO40391Yes
2745 >AR: Block 4th and higher AR-
cycles (>BLK 4.-n. AR)
Auto Reclose SP on
off
**LEDBIBO40401Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation