Appendix
A.8 Information List
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
722
2909 >Sync-Prog. Usy1<Usy2>
(>Usy1<Usy2>)
Sync. Check SP * * * LED BI BO
2910 >Sync-Prog. Usy1<Usy2<
(>Usy1<Usy2<)
Sync. Check SP * * * LED BI BO
2911 >Sync-Prog. Override ( bypass )
(>Sync. o/ride)
Sync. Check SP * * * LED BI BO
2930 Synchro-check ON/OFF via BI
(Sync. on/off BI)
Sync. Check IntSP on
off
**LEDBO
2931 Synchro-check is switched OFF
(Sync. OFF)
Sync. Check OUT on
off
**LEDBO41311Yes
2932 Synchro-check is BLOCKED
(Sync. BLOCK)
Sync. Check OUT on
off
on off * LED BO 41 32 1 Yes
2934 Synchro-check function faulty
(Sync. faulty)
Sync. Check OUT on
off
**LEDBO41341Yes
2935 Synchro-check supervision time
expired (Sync.Tsup.Exp)
Sync. Check OUT on on * LED BO 41 35 1 No
2936 Synchro-check request by control
(Sync. req.CNTRL)
Sync. Check OUT on on * LED BO 41 36 1 No
2941 Synchronization is running (Sync.
running)
Sync. Check OUT on
off
on * LED BO 41 41 1 Yes
2942 Synchro-check override/bypass
(Sync.Override)
Sync. Check OUT on
off
on * LED BO 41 42 1 Yes
2943 Synchronism detected (Synchro-
nism)
Sync. Check OUT on
off
**LEDBO41431Yes
2944 SYNC Condition Usy1>Usy2<
true (SYNC Usy1>Usy2<)
Sync. Check OUT on
off
**LEDBO41441Yes
2945 SYNC Condition Usy1<Usy2>
true (SYNC Usy1<Usy2>)
Sync. Check OUT on
off
**LEDBO41451Yes
2946 SYNC Condition Usy1<Usy2<
true (SYNC Usy1<Usy2<)
Sync. Check OUT on
off
**LEDBO41461Yes
2947 Sync. Voltage diff. greater than
limit (Sync. Udiff>)
Sync. Check OUT on
off
on off * LED BO 41 47 1 Yes
2948 Sync. Freq. diff. greater than limit
(Sync. fdiff>)
Sync. Check OUT on
off
on off * LED BO 41 48 1 Yes
2949 Sync. Angle diff. greater than limit
(Sync. ϕ-diff>)
Sync. Check OUT on
off
on off * LED BO 41 49 1 Yes
2951 Synchronism release (to ext. AR)
(Sync. release)
Sync. Check OUT * * * LED BO 41 51 1 Yes
2961 Close command from synchro-
check (Sync.CloseCmd)
Sync. Check OUT * * * LED BO 41 61 1 Yes
2970 SYNC frequency fsy2 > (fn +
3Hz) (SYNC fsy2>>)
Sync. Check OUT on
off
on off * LED BO
2971 SYNC frequency fsy2 < (fn +
3Hz) (SYNC fsy2<<)
Sync. Check OUT on
off
on off * LED BO
2972 SYNC frequency fsy1 > (fn +
3Hz) (SYNC fsy1>>)
Sync. Check OUT on
off
on off * LED BO
2973 SYNC frequency fsy1 < (fn +
3Hz) (SYNC fsy1<<)
Sync. Check OUT on
off
on off * LED BO
2974 SYNC voltage Usy2 >Umax
(P.3504) (SYNC Usy2>>)
Sync. Check OUT on
off
on off * LED BO
2975 SYNC voltage Usy2 < U>
(P.3503) (SYNC Usy2<<)
Sync. Check OUT on
off
on off * LED BO
2976 SYNC voltage Usy1 >Umax
(P.3504) (SYNC Usy1>>)
Sync. Check OUT on
off
on off * LED BO
2977 SYNC voltage Usy1 < U>
(P.3503) (SYNC Usy1<<)
Sync. Check OUT on
off
on off * LED BO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents