Appendix
A.8 Information List
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
735
4083 DisTel Blocking: carrier STOP
signal, L2 (Dis.T.BL STOPL2)
Teleprot. Dist. OUT * * * LED BO
4084 DisTel Blocking: carrier STOP
signal, L3 (Dis.T.BL STOPL3)
Teleprot. Dist. OUT * * * LED BO
4160 >BLOCK Power Swing detection
(>Pow. Swing BLK)
Power Swing SP on
off
on off * LED BI BO
4163 Power Swing unstable (P.Swing
unstab.)
Power Swing OUT on on * LED BO
4164 Power Swing detected (Power
Swing)
Power Swing OUT on
off
on off * LED BO 29 164 1 Yes
4166 Power Swing TRIP command
(Pow. Swing TRIP)
Power Swing OUT on on * LED BO 29 166 1 No
4167 Power Swing detected in L1
(Pow. Swing L1)
Power Swing OUT on
off
on off * LED BO
4168 Power Swing detected in L2
(Pow. Swing L2)
Power Swing OUT on
off
on off * LED BO
4169 Power Swing detected in L3
(Pow. Swing L3)
Power Swing OUT on
off
on off * LED BO
4177 Power Swing unstable 2 (P.Swing
unst. 2)
Power Swing OUT * * * LED BO
4203 >BLOCK Weak Infeed (>BLOCK
Weak Inf)
Weak Infeed SP * * * LED BI BO
4204 >BLOCK delayed Weak Infeed
stage (>BLOCK del. WI)
Weak Infeed SP on
off
on off * LED BI BO
4205 >Reception (channel) for Weak
Infeed OK (>WI rec. OK)
Weak Infeed SP on
off
on off * LED BI BO
4206 >Receive signal for Weak Infeed
(>WI reception)
Weak Infeed SP on
off
on off * LED BI BO
4221 Weak Infeed is switched OFF
(WeakInf. OFF)
Weak Infeed OUT on
off
**LEDBO25211Yes
4222 Weak Infeed is BLOCKED (Weak
Inf. BLOCK)
Weak Infeed OUT on
off
on off * LED BO 25 22 1 Yes
4223 Weak Infeed is ACTIVE (Weak Inf
ACTIVE)
Weak Infeed OUT * * * LED BO 25 23 1 Yes
4225 Weak Infeed Zero seq. current
detected (3I0 detected)
Weak Infeed OUT on
off
on off * LED BO
4226 Weak Infeed Undervoltg. L1 (WI
U L1<)
Weak Infeed OUT on
off
on off * LED BO
4227 Weak Infeed Undervoltg. L2 (WI
U L2<)
Weak Infeed OUT on
off
on off * LED BO
4228 Weak Infeed Undervoltg. L3 (WI
U L3<)
Weak Infeed OUT on
off
on off * LED BO
4229 WI TRIP with zero sequence
current (WI TRIP 3I0)
Weak Infeed OUT * * * LED BO
4231 Weak Infeed PICKED UP (Weak-
Inf. PICKUP)
Weak Infeed OUT * off * LED BO 25 31 2 Yes
4232 Weak Infeed PICKUP L1 (W/I
Pickup L1)
Weak Infeed OUT * on * LED BO
4233 Weak Infeed PICKUP L2 (W/I
Pickup L2)
Weak Infeed OUT * on * LED BO
4234 Weak Infeed PICKUP L3 (W/I
Pickup L3)
Weak Infeed OUT * on * LED BO
4241 Weak Infeed General TRIP
command (WeakInfeed TRIP)
Weak Infeed OUT * * * LED BO 25 41 2 No
4242 Weak Infeed TRIP command -
Only L1 (Weak TRIP 1p.L1)
Weak Infeed OUT * on * LED BO 25 42 2 No
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation