Connection recommendations
Use a fuse for the signal output (max. 10 A).
Provide protection for relay contacts to protect the device against spikes if inductive
loads are connected.
Precautions
Before opening the lid, ensure there are no dust deposits around
SITRANS LVS100/200, and that the atmosphere around the instrument is settled.
Make sure the main voltage does not exceed the maximum voltage listed on the
product label.
Ensure that no more than 8 mm of each wire is stripped (to avoid danger of contact
with live parts).
Ensure the boots for protecting cable terminations are no longer than 8 mm (to avoid
danger of contact with live parts).
For installation of the 3-wire PNP electronics (Protection Class III), the insulation of
the connected power supply and output load must meet the relevant standards.
Universal voltage (DPDT relay)
(LVS100)
alarm output relays
FSH/FSL adjustment
sensitivity adjustment
B = factory setting,
A = decreased sensitivity
AC: terminal 1: L
terminal 2: N
19 to 230 V AC, ± 10 %,
50 to 60 Hz, 22 VA
DC: terminal 1: +
terminal 2: -
19 to 40 V DC, ± 10 %, 2 W
LED
protective
earth
terminal
fuses: max. 10 A, fast or slow,
HBC, 250 V