Page EN-22 SITRANS LVS100/200 – INSTRUCTION MANUAL 7ML19985FT63
mmmmm
English
Signal output and test options (LVS200)
Signal Output Delay
Universal voltage (DPDT) model
The signal output can be delayed and is adjustable from 0 to 30 seconds. Turn the
potentiometer clockwise to increase the delay time.
Potentiometer T1: Delay when output switches from fork covered to uncovered.
Potentiometer T2: Delay when output switches from fork uncovered to covered.
Test function
NAMUR model (IEC 60947-5-6) and 8/16 mA or 4 to 20 mA model
If the fork is uncovered, pressing this button will stop the vibration and the signal output
will switch to indicate a covered fork. You can test the vibration and the electronics
without removing the LVS200 from the vessel. If the fork is covered, pressing the button
has no effect.
Note: The signal output and test options listed below apply only to specific power
supply options.
Test button
Electronic module
diagnostic LED
NAMUR model
sensitivity adjustment:
B = factory setting
A = decreased sensitivity
A
B