7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 95
mmmmm
H: Parameters
2.7.8. TVT shaper
A breakpoint on the TVT curve, normalized to 0.
2.7.8.1. Shaper A (1-9)
2.7.8.2. Shaper B (10-18)
2.7.8.3. Shaper C (19-27)
2.7.8.4. Shaper D (28-36)
2.7.8.5. Shaper E (37 - 40)
2.7.9. Rate
2.7.9.1. Fill Rate (default 0.1)
Defines the maximum rate at which the reported sensor value is allowed
to increase. Allows you to further adjust the Probe LU response to
increases in the actual material level (or an advance to a higher Failsafe
Material Level, P071). Fill Rate is automatically updated whenever
Response Rate is altered.
Enter a value slightly greater than the maximum vessel-filling rate, in
Sensor Units per minute.
2.7.9.2. Empty rate (default 0.1)
Defines the maximum rate at which the reported sensor value is allowed
to decrease. Adjusts the Probe LU response to decreases in the actual
material level. Empty Rate is automatically updated whenever Response
Rate is altered.
Values
Range: 0.0000 to 99999 m/min.
Altered by
Response Rate
Related
Unit (Level)
High Level Point
Hand Programmer Value Meters/Minute
1* 0.1
21
310
Values
Range: 0.0000 to 99999 m/min.
Altered by
Response Rate
Related
Units (Level)
High Level Point