7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 97
mmmmm
H: Parameters
Open the menu Device – Simulation, go to Function Block – AIFB1 or 2, click on
the tab Simulation Output, and select a target mode. Then click on the tab
Simulation (Measured Value), and enable or disable Simulation.
3.1.2. Unit (default %)
Defines the engineering unit to be displayed with the output value.
3.1.3. Filter Time Constant (default 10)
Contains the time constant for the damping filter. The engineering unit is always
in seconds. (This is an exponential filter: when a change occurs at the input, the
output will be at 63.2% of the change in one time constant, and will be at full
change after 5 time constants.)
3.1.4. Function (default PV)
Used to select between the different Level Transducer Block outputs (Volume/
Level, Level, Distance in Sensor units, Distance in Level units).
3.1.5. Batch Information
These 4 parameters are intended to be used in Batch Applications conforming to
IEC 61512 Part 1 (ISA S88). Other applications do not require these values, which
are only stored in the Function Block.
3.1.5.1. Batch ID (default 0)
Identifies a certain batch to allow assignment of equipment-related
information (for example faults, alarms) to the batch.
3.1.5.2. Batch Unit (default 0)
Identifies the active Control Recipe Unit Procedure or the related Unit (for
example, reactor, centrifuge, drier).
3.1.5.3. Batch operation (default 0)
Identifies the active Control Recipe Operation.
3.1.5.4. Batch Phase (default 0)
Identifies the active Control Recipe Phase.
Note: If Target Mode has been changed locally and you want to prevent an
external process from resetting it back to normal, you should ensure
Remote
Lockout
(see page 74) is set to Locked.