EasyManua.ls Logo

Siemens sitrans PROBE LU - Mechanical and Interface Specifications

Siemens sitrans PROBE LU
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 8 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JB02
mmmmm
Specifications
Update time
1
12 mA loop current 6.0 s (typical), maximum 16.0 s
13 mA loop current 5.0 s (typical), maximum 14.0 s
15 mA loop current 3.7 s (typical), maximum 8.0 s
20 mA loop current 2.4 s (typical), maximum 4.0 s
Beam angle 10° at –3 dB boundary
Temperature compensation built in to compensate over temperature range
Memory
non-volatile EEPROM
no battery required
Interface
PROFIBUS PA
configuration Siemens SIMATIC PDM (PC),
or Siemens infrared handheld programmer
display (local) multi-segment alphanumeric liquid crystal with bar
graph (representing level)
Mechanical
Process Connections
threaded connection 2” NPT, BSP, or G (BS EN ISO 228-1) /PF
flange connections 3" (80 mm) universal flange
other connections FMS 200 mounting bracket, or customer-supplied
mount
Transducer (2 options)
ETFE (ethylene-tetrafluoroethylene), or
PVDF (polyvinylidene fluoride)
Enclosure
body construction PBT (polybutylene terephthalate)
lid construction PEI (polyether imide)
conduit entry 2 x M20x1.5 cable gland, or 2 x 1/2" NPT thread
ingress protection Type 4X/NEMA 4X, Type 6/NEMA 6, IP67, IP68
2
(see
note below regarding approved hubs)
Weight
Standard model 2.1 kg (4.6 lb)
1.
Temperature dependent: typical value at +20 °C (+68 °F); maximum value at +80 °C (+176 °F)
2.
Submergence test under water at 2 m (6.5 ft) depth for 24 hours.

Table of Contents

Other manuals for Siemens sitrans PROBE LU

Related product manuals