EasyManua.ls Logo

Siemens Static Trip III - Ground Fault Sensing Diagrams

Siemens Static Trip III
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ground
Fault
Sensing
Diagrams
Ground
Fault
Sensing
Diagrams
iH"lriiirj^*Ln
-0"
"oit'g";;
to
accommodate
the
followins
oround
faulL
sensing
scnemes'
I
3-Pha.",
3-Wire
Residual
.
3-Phase,
4-Wire
Residual
.
Direct
Ground
.
ZeroSequence
The
following
are
brief
descriptions
of
the
ground
f ault
sensing
schemes
as
they
r"rutu
iJir'5
siatic
Trip
l'il
trip
units
Detailed
technical
and
applicatiJn
rnfot"tion
on
the.
oround
fault
sensino
schemes
i.
"onilin"iln
in?
s-i"nn"nt
rlitrical
Prod-
uits
Siecitication
Guide
(SG 3061)'
Residual
(3-Phase,
3-Wire)
-
Under
normal
system
conditions'
(withoul
the
presence
oiu
gto;O
l'yl.:f ,vector
sum
of
thenhaseCUrrentsbelngmonitoredbythetripunitiszero.This
i."rf#i;;i;;;;
th;
Jondition
of
ah
overc.urrent
phase-to-
ohase
fault
and
phase t'nOutun""
condrtion
When
a
phase{o-
Xl';;;ii;;ii";i*i,
L1"""ioi
"'
or
the
phase
currents
is
Xl;:i,,
f
t"p"iiiiJi,o
tne
magnitude
or
the
sround
rault
rhe
trip
unit's
microprocessot
"Jt
this
vector
sum
data
in
the
execution
of
the
grounJiu*
ptt""tion
function
The
trip
unit
,illr"tiH"
,i"in"ur
nt"ux"i
current
sensors
No
external
cur-
rent
sensors
are
required'
Circuit
breaker
current
sensors
are
available
with
separate
2000A
grouno sensor*]iJ'gi
t"
Orovile-tt1
1200A
maxi-
;"u"ri';;";;;-fault
pickup
'"itins
iequired
bv
NEC
Article
230-95
for
service
"ntt'i""
app-lications
Wiring
diagrams
for
the
two
3-Phase,
i-Wit"
glo'1d
fa{!
sensing
schemes
are
given in
the
Curre'nt'S"ntlot
Wiring
Diagrams
section
ln
either
case,
tr,e
curreni
t"ntott
are
ilounGd
on
the
circuit
6t"rx"t.
N.i
external
current
sensors
are
required'
Residual
(3-Phase,
4-Wire)
-
ln
the
3
Phase'^4
Wire
Residual
scheme
a
fourth
",""nt-J"nior
is
connected
in
the
neutral
conductor
to
Sense"lormat
neutrat
currents
Under
normal
svstem
conditions
tf'e
vector
sum
of
the
currents
in
all
phases
:'"",;;i.';;
.;;i;rl
;r;;;iThis
is also
true
under
the
condition
;i#;";;"r;[n]
pr'tut"
io-phase
fault
and
phase
unbalance
condition.
When
a
phase-to-ground
fault
occ-Lrrs'
the
fault
current
returns
uiu
u
putt't"Jtf'Lrif'an
tfre
neutral'
Therefore'
the
vector
sum
of
the
phaJe
currents
no
longer
equals
the
neutral
current.
frris
c'lrieni
ditferentiat
is
detected
by
the
i,",'t.*it
*J
uied
in
the
execution
of
the
ground
fault
pro-
i"E,i""
i,l".i,Jn.
6rr.,."ni
#n#i
wit.t
separate
2000A
NEC
;;;;;st-
,;;-usable
toi
t"n's
ilnsins
scheme'
iust
as
for
3-
pHr.","5
wiie
residual
giorno
sens'ing
(see
current
sersor
Wiring
Diagrams),
Direct
Ground
-
ln
this
scheme'
the
phase
c,urrents
are
not
used
in
detecting
unO
plJ""ittg
grornd
faults
The
trip
unit
;H.ji;;
il;g';,,n0
ti'ii
p'Li""iiJ"
runcrron
based
on
data
from
a
ground
current
Jenloi
if
':
:"L:.:^t^is
located
on
the
neutral
connection
to
gio'nO
at
the
service,entrance'
and
is
connected
to
tne
appr6[t't"l"p't
terminals
on
the
trip
unit
(see Current
Sensor
Wiring
lJiagrams'7
Zero
Sequence
-
This
scheme
is
very
similar
to
the
Residual
6"rlirll"i|le
traoitionaimethod
is
touse
a
core
balance
tvpe
current
sensor
wf,icn
lncircl6s
all
phase
conductors
and
neutral
on
a
four
wire
tVJ"'
UnO"r
nolmal
:I:t"'
conditions
"t
"
rf.lrt"
i"-phase
iauti
conOltion'
there
is
no
output
from
;h"'#;r;;
i"
TH"
liip
,"ii
o"ta"e
the
vector
sum
of
the
currents
through
tne
selsor
winJow
is
z.ero.,lf
a
ground
fault
occurs,
the
ground
"'ii"i
it
not
s""n
by,the
sensor'
which
t*,".
tl,
,f-rJ
*,t""
by
I
patn
ottrer
than
through
the
sensor
*"i"d;.1'h;."n.o,
oZt"its
this
current
rmbalance
and
pro-
vides
the
data
requirei'OV
jn"
tiip
unit
to
execute
l?
g]"^Y:d
irr["pi"t#i"n
lunction
The
zeto
sequence
sensor
rs
con-
nected
to
the
appropiut"
inp't
t"tminals
of
the
trip
unit
(see
Crii"nt
Sensor'Wirlng
Diagrams)'
Alternatively,
three
orfour
current
sensors
orstandard
CT's
can
be
connected
togetnll,
"
*'tft
the
Besidual
Schemes
de-
scribed
above.
tn
tl^'ls
JasJ]ho*"u"t'
only
the
electrlcal
sum
of
the
sensor
outputs
it"it"lj
us
Jite"t
input
to
the
trip
unit's
oround
fault
circuit
tlrminats
(the
sensors
are
not
used
for
X;;u.
";;;"i
l.prtl"iHills
tr'e
etectrical
equivalent
of
the
it;;il;;i
.ugndti"'"o,,e
balance
summation'
Breaker
Mtd
C!rrefl
Sensors
N.!lral
Bus
Cur:ent
Sensors
Residual
Sensing,
Circuit
Breaker
Wiring
for
Ground
Protection
(3-
Phase,
4-Wire
SYstem
Shown)
18
Direct
Ground
Current
Sensing
Aiernate
Pcs
t
on Oi
Zero
Seque:.e
Sefso'
Nelta
D
sconnact
Lnr
Zero
Sequence
Ground
Fault
Protectlon

Table of Contents

Related product manuals