.af
Accessories
Breaker Position 
Switch
A spring-loaded switch 
is 
used 
for circuit breaker open/closed
position 
input 
to static 
Trip lllc/cP/cPX  trip units 
The switch
assembly 
is designed for simple 
mounting 
to 
Type RL circuit
breakers,  but can 
be used for retrofit to other circuit 
breakers
as well. The switch  is wired to the 
trip unit as a 52b contact 
so
that an open connection 
will 
appear 
as a closed breaker.
Position switch  mounted  on Type 
RL 
circuit breaker
!nterposing 
Relay
An interposing  relay is required  to 
integrate 
the Static 
Trip lllC/
CP/CPX 
model trip units' 1OOmA 
12V 
dc Output 
1 signal 
into
alarm or control schemes. 
The interposing  relay 
provides 
a 1A
12OY 
acl125Y dc 
normally open solid state  contact 
and can be
mounted in the circuit breaker  compartment.
Interposing  Relay 
mourited  in Type  RL circuit breaker  compartment.
Potential 
Transformers
Two 
potential 
transformer 
models are 
available 
for use 
with
power 
metering 
version 
Static 
Trip lll devices. 
The catalog
number 
PTN/-A is designed 
for integral 
mounting  on 
type
RL low voltage 
power 
circuit breakers; 
the 
PTM-B  uses 
a more
general  purpose 
mounting which 
is 
better 
suited 
for retrofit
applications. 
Kits are available 
which 
include  the 
PT 
module,
wire and 
primary 
fuse assemblies 
for upgrading 
Type RL,
circuit breakers 
or 
installation on other 
manufacturers
equipment.
t
(
Installed  Potential 
Transformer  on 
Type RL breaker
46