Metering 
and 
Extended 
Protective Relaying
U
Fundamental 
Conf 
i 
guration 
Parameters
The 
parameters 
described 
in 
this 
paragraph 
must be set for
proper 
operation 
of the trip unit. 
They affect fundamental
communications  and metering functions.  Parameters  that 
must
be set 
for 
a 
given 
trip unit model are indicated 
with 
a 
(+) 
in 
the
following 
table.
Fundamental 
Conf 
iguration Parameters
Address 
- 
The Address 
must be set 
for 
all communicating
model 
types. 
Valid 
ranges are 
1 
through 
224.fheIrip 
units 
are
shipped 
from 
stock at address 
222. llis recommended that
only addresses 1 
through 
221 
be used 
in an installation,  Each
trip unit connected on the same  network  must 
have 
a unique
address. 
The 
address 222 is also suggested as the 
"parking"
address of any 
trip unit taken out of service.
Baud Rate 
- 
Alltrip 
units connected on the same 
network must
have 
the same  baud 
rate. Valid 
selections 
for Baud Rate are
2,4OO,4,800, and 
9 600 baud. 
The 
trip 
units are shipped from
the 
factory set for 4,800 
baud.
Phase  Sensor  Rating 
- 
The Phase  Sensor 
rating 
(or 
I 
SCALE)
must 
be set equal  to the 
primary 
ampere 
rating 
of the 
current
sensor 
on the 
circuit breaker 
in which  the trip unit is installed.
Example:  lf the current  sensor  is rated at 800 Amps 
(800/0 
5)
then 800 
would 
be the value used 
for 
the 
Phase 
Sensor 
Rating,
This number 
affects the 
values 
displayed 
for the metered
currents 
la, lb, lc 
and 
ln 
(if 
ordered).  On CP 
models it also
affects the values displayed for kW, kVA, 
kVAR kWH kVARH
kWHR,  and kWD, lt also affects the operation  of any current 
or
power 
based alarm 
and 
relaying  functions.  The normal 
range
of the Phase Sensor  Rating  is 80 to 4,000.
Ground  Sensor 
Rating 
- 
The 
Ground 
Sensor rating 
(or 
G
SCALE) 
must 
be set equal to the 
primary 
ampere 
rating 
of 
the
ground 
sensor used by the circuit breaker 
for 
ground 
fault
sensing. Example:  lf 
the 
ground 
sensor 
is rated at 800 Amps
(800/0 
5) then 800 would be the value used for the Ground
Sensor 
Rating. This number 
affects the 
values 
displayed 
for
the metered  current lg. lt also affects  the operation  of the
ground 
current based alarm function.
Phase Rotation 
- 
The Phase Rotation must 
be set 
to the
phasing 
of the system in which  the circuit breaker  is installed.
It may be set to ABC 
(normal phasing) 
or ACB 
(inverted
phasing) 
The 
setting affects 
values displayed 
for the 
voltages,
kW, kVAR, kWH kWHR, kVARH and 
kWD, It also affects 
the
operation 
of any voltage or 
power 
based 
relaying 
functions.
Volts 
Source 
- 
The Volts 
Source 
is settable  to 
Top or Bottom.
It 
should  be set 
to Top if the 
powei 
source 
is fed 
into 
the 
top of
the circuit 
breaker; Bottom 
if 
the 
power 
source 
is fed into the
bottom.  This setting affects 
the displayed sign 
of the kW and
kVAR 
readings.  lt 
also 
affects the accumulated 
values 
for kWH,
kWHR 
kVARH 
and 
kWD and the operation 
of any associated
alarm and 
relay functions.
Volts 
Scale 
- 
The Volts Scale 
is normally set to the 
nominal 
line-
line voltage 
(2O8, 
240,380 480 or 600) of 
the system 
The
value is 
used only 
by the voltage unbalance 
alarm and 
relay
functions. lt does 
not 
affect  the 
displayed 
voltage values.
Volts 
Mode 
- 
The Volts Mode is settable 
to 3-Wire or 
4-Wire.
Use 3-Wire 
when there is no 
neutral connection 
in 
the 
system;
otherwise, 
use 4-Wire. In 3-Wire 
mode, 
phase 
to 
neutral
voltages  will not be 
measured  or displayed.
kW 
Demand  Period Length and 
Number 
of 
Periods 
- 
De-
mand  Period Length  is settable 
from I to 99 
minutes.  Number
(of 
) 
Periods is settable 
f rom 1 
to 
15. This allows 
for f ixed interval
or sliding  window 
methods  of demand  calculation. 
For the
fixed 
interval, 
set the 
Length  to the desired 
time and 
set
the 
Number 
of 
Periods to 1 . For the sliding 
window 
method,  set
the 
Length and the Number of 
Periods such that 
their 
pro-
duct equals the desired demand 
interval.
Comm 
Trip 
- 
The Comm 
Trip is 
settable 
to either On 
or Off 
. All
communications trip units are 
capable  of tripping 
the circuit
breaker via a series  of commands 
from a 
master  device 
us-
ing the RS-485  bus. Comm 
Trip must be 
set to On 
for the
command  sequence 
to be recognized 
and a trip to 
occur.
Remote tripping of the circuit breaker 
is stored 
in 
the 
trip unit's
event 
log. The Comm 
Trip 
setting 
does not affect 
the operation
of any of the trip unit's 
protection 
functions, neither the 
basic
nor 
the extended 
functions.
Comm 
Close 
- 
The 
Comm 
Close 
is 
settable 
to either On 
or Off .
All communications 
trip units are capable 
of closing  the 
circuit
breaker 
via a series of commands 
from a master device 
using
the RS-485 bus. Comm  Close 
must be 
set to On 
for the
command sequence 
to be recognized 
and a closure 
to
occur. 
Remote  closing of the circuit 
breaker 
is 
stored 
in the
trip unit's event  log. 
A 
special 
Anti-Pump 
"Y" 
Relay is used to
integrate  the Output 
2 
(close 
breaker) signal 
into electrically
operated 
Type RL breaker 
wiring 
(see 
Instruction 
Manual
SG3068 
for details),
Comm Open 
- 
The 
Comm Open 
is settable  to 
either On or Off 
.
When used with the appropriate 
interposing 
relay, communi-
cations  trip units are capable 
of opening an 
electrically oper-
ated circuit 
breaker  via a series  of commands 
from a 
master
device 
using the RS-485 bus. Comm 
Open 
must be set to On
for the command sequence 
to be recognized 
and an opening
to occur, 
Remote 
opening 
of the circuit breaker 
is stored 
in 
the
trip unit's 
event log.
Parameler
Trip 
Unit 
Model
iltc/cN iltcP/cNP/cPx/cNPx
AOO rESS
Baud  Rate
Phase Sensor  Ratrng
Ground  Sensor  Rating
+
+
+
+
+
+
+
+
Phase  Fotation
Volts Source
Volts Scale
Voits lvlode
Demand  Per od Length
Number  of Periods
+
+
+
+
+
+
Cornm 
Tr 
p
Comm  C ose
Comm  Open
t
+
+
+
+
+
rb/
27