Metering
and Extended
Protective
Relaying
I
ib/
Metering Functions
The
metered
and logged
parameters
of Static Trip lllC/CP/CPX
trip units may
be monitored
remotely
over
the communications
bus
or locally
with the Breaker
Display
Unit
(see
Breaker
Display
Unit
section). The
specifications
of the metered
para-
meters
are
given
in
the following
table.
The real{ime
and
min/max
values
represent
averages of
each measured
para-
meter
over approximately
one second.
Measured
Parameters
Specif
ications
Parameter
Description
Phase
Currents Measured
RMS
Value
of each
Phase
Current
Range:
0
to
1000%
of Phase
Current
Accuracy:
:"i;::?'xi3!'"H'i$,.,,",
I
0% to 125%
of Phase
Sensor
BDU Display:
la
=
XXXX
lb
=
XXXX
lc
=
XXXX
Average
Phase
Arithmetic
Average
of Phase
A, Phase
B,
Current
and Phase
C Currents
BDU Display:
l*
=
YXXX
Ground
Current Measured
RMS
Value
of Ground
Current
Range
0 lo 125%
of Ground
Sensor
Primary
Rating
Accuracy:
+17"
of Ground
Sensor from
10%
to
125%
of
Ground Sen-
BDU
Disptay: ij't=
*ru
Neutral
Current
Measured
RMS Value
of Neutral
Current
Range:
0 to 1000%
of Neutral
Current
Sensor Primary
Rating
Accuracy:
+1"/"
of Neutral
Sensor from
10%lo
125%
of Neutral
Sensor
BDU Display:
ln
=
XXXX
Phase Voltages
Measured
RMS Value
of each
Phase
Voltage
(4
Wire
Mode
only)
Range
0 to 380 Volts
Accuracy:
!1%
of
reading
from 70
to
380 Volts
BDU
Display: Va
=
XXX
Vb
=
XXX
VC
=
XXX
Arithmetic
Average
of A, B
and C
Phase
Voltages
(4-Wire
mode
only)
BDU
Display:
V*.= XXX
Measured
RMS Value
of
each Line to
Line
Voltage
(3-Wire
and 4-Wire
Modes)
Range:
0
to 660 Volts
Accuracy:
!1%
of
reading
from
I20 to
660 Volts
BDU Display:
Vab
=
XXX
VbC
=
XXX
VCa
=
XXX
Arithmetic
Average
of A-B B-C,
and C-A
Line
to Line Voltage
BDU Display:
VXX
=
XXX
Description
Measured Line Frequency
taken from
Phase
A Voltage
Range:
45.0 to 70.O Nz
Accuracy:
!.25%
of
reading
provided
Va
is above 90V,
BDU
Display: Hz
=
XX.X
Signed
Sum of the Measured Real Power
of all 3 Phases in
Kilowatts
Range: x7,200
(Normally
Limited
by
Breaker
Size)
Accuracy:
+2%
of
Reading
provided
power
factor
is
greater
than
50% and current and voltage
signals are within their speci-
fied accuracy ranges.
BDU Display:
kW
=
XXXX
Signed
Sum of the Measured Power
of all
3
Phases
in Kilovars
Range: 17,200
(Normally
Limited by
Breaker
Size)
Accuracy:
t2% of Reading
provided
power
factor is less
than
90% and current and voltage
signals are within their speci-
fied accuracy ranges.
BDU Display:
kQ
=
XXXX
Sum of the Apparent
Power of all 3
Phases
in Kilovolt Amperes
Range:
O Io 7
,2O0
(Normally
Limited
by Breaker
Size)
Accuracy:
t2%
of
Reading
provided,
current and voltage signals
are within
their specified ac-
curacy ranges.
BDU Display: kVA
=
XXXX
Ratio
of Real Power
to
Apparent
Power
Range:
-.99
to
.1.00
Accuracy: .04
between .50 leading and
.50 lagging
provided
current
and voltage
signals are
within their specified
accu-
racy ranges.
BDU
Display: PF
=
X.XX
Signed Accumulation of Real Energy in
1000's
of
Watt
Hours
Range:
0tot9999,999KilowattHours
Accuracy:
+2%ofReading
BDU Display:
kWh
=
XXXX
(or
MWh
=
XXXX)
Accumulation
of Real Energy in 1000's
of
Negative
Watt Hours
Range:
0 to t9,999,999 Kilowatt
Hours
Accuracy:
x2%
of Reading
BDU
Display:
-kwh
XXXX
(or
-MWh
XXXX)
Signed Accumulation
of
Reactive
Energy
in I000's
of
VAR
Hours
Range:
0tot9,999,999KiloVARHours
Accuracy:
+27"
of
Reading
BDU Display:
kQh
=
XXXX
(or
MQh
=
XXXX)
Parameter
Frequency
Real Power
Reactive Power
Apparent
Power
Power Factor
Kilowatt
Hours
Kilowatt
Hours
Reverse
Average
Phase
Voltage
Line Voltages
Average
Line Voltage
r-U
KiloVAR
Hours
21

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Static Trip III and is the answer not in the manual?

Siemens Static Trip III Specifications

General IconGeneral
BrandSiemens
ModelStatic Trip III
CategoryCircuit breakers
LanguageEnglish

Related product manuals