TX-I/O Modules
Address Keys
I/O modules are addressed using a TX-I/O address key.
TXIO0062R1
Reset Key
TX-I/O Address Keys.
The keys are available in sets of 24, up to a maximum value of 72 (2 sets of 12, 1-24,
25-48, and 49-72).
The I/O module address is mechanically encoded in the address key.
Without an address key, the module is inactive.
With an address key inserted, the module has full functionality.
Based on the address, the TC Modular or TC-36 configures the I/O module,
indicates which field devices are connected to this module, and which function is
required for the field devices.
CAUTION
The address key must be inserted firmly into the terminal base before swiveling it
into the plug-in module.
1
TXIO0039R1
2
TXIO0040R1
14
Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference
588-587 CONFIDENTIAL: For internal use only 4/6/2010