EasyManuals Logo

Siemens TALON TXM1.16D User Manual

Siemens TALON TXM1.16D
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Troubleshooting the TX-I/O Island Bus
49
Siemens Industry, Inc. TALON TX-I/O Modules and Island Bus Technical Reference
588-587 CONFIDENTIAL: For internal use only 4/6/2010
If too many of these outputs are configured, the voltage may drop too much so that all
modules switch off. When the voltage recovers, the modules switch on again, and so
forth, 1 to 2 times per second.
In this case, the TC Modular or TC-36 reacts by switching off the communication after
5 cycles (shortcut between CD and CS, the COM LED will light brightly).