CCP 611 C-DIAS PROSESSOR MODULE
Page 30 27.03.2020
An error number was entered In the
VARAN Manager and stopped the
program.
Possible Causes:
- real network does not match the
project
Solution:
Read logfile
A required VARAN client was
disconnected or communication
error has occurred. The program
was stopped.
Possible Causes:
- damaged wiring
- missing power supply for decentral-
ized modules
Solution:
Read logfile
- analyze error tree
An error has occurred while loading
the application.
An error has occurred while attempt-
ing to save the application.
Read-write access to prohibited
memory area, e.g. writing to NULL
pointer.
An exception error caused by
exceeding the memory limits
An unauthorized instruction for the
current CPU level was given. For
example, setting the segment
register.
An error has occurred during a
floating-point operation.
Error from the Intelligent DIASMas-
ter.
An internal error has occurred, all
applications are stopped.
Restart; report error to Sigmatek.
An error has occurred during a file
operation.
Restart; report error to Sigmatek.
The total duration of all real-time
objects exceeds the maximum time;
the time cannot be configured.
2 ms for 386 CPUs
1 ms for all other CPUs
Starting from Version 1.1.7