press the button
t
to scroll up the list of parameters and
then
r
to scroll down the list
NB:
holding the buttons
r
or
t
increases the speed of the
scrolling movement.
once the required parameter has been reached, press
the buttons
>
or
<
to modify the value within the permitted
range. The modifications are stored automatically.
When all the parameter modifications have been made, exit
the parameter menu by pressing and holding down the but-
tons
r
and
t
at the same time
until the initial screen is dis-
played.
3.4 List of parameters
Type No. Description Range
Unit of
meas-
urement
Step Default
CONFIGURATION
PAR 01
Index showing boiler power in kW
0 = 24; 1 = 30; 2 = 40
0 .. 2 - 1 0 or 1
PAR 02
Hydraulic configuration
0 = rapid
1 = hot water tank with thermostat
2 = hot water tank with sensor
3 = two programmer
0 .. 3 - 1 0
PAR 03
Gas Type Configuration
0 = G20; 1 = LPG
0 .. 1 - 1 0 or 1
PAR 04
Combustion configuration
0 = sealed chamber with combustion control
1 = open chamber with smoke thermostat
0 .. 1 - 1 0
PAR 07 Ignition power 0 .. 40 - 1 0
PAR 08 External sensor value correction -5 .. +5 °C 1 0
DOMESTIC HOT WATER - HEATING
PAR 10 Boiler Antifreeze Threshold 0 .. +10 °C 1 3
PAR 11 External Sensor Antifreeze Threshold
-9 .. +5
-- = Disabled
°C 1 -2
PAR 12 Heating Curve Incline 0 .. 80 - 1 20
PAR 13 Minimum Heating Temperature Adjustment 20 .. Par tS 1.4 °C 1 20
PAR 14 Maximum Heating Temperature Adjustment Par tS 1.3 .. 80 °C 1 80
PAR 16 Heating Post-Circulation Time 0 .. 99
seconds
x 10
1 3
PAR 17 Heating Pump Activation Delay 0 .. 60
seconds
x 10
1 1
PAR 18 Re-ignition Delay 0 .. 60 Min 1 3
PAR 19 Domestic Hot Water Modulation with Flow meter
-- = Disabled
1 = Enabled
- - 1
PAR 26 Zone Valve / Pump Relaunch Delay 0 .. 99 Min 1 0
PAR 29 Anti-legionella Function (Only hot water tank)
-- = Disabled
50 .. 80
- 1 --
PAR 35
Digital / analogue Pressure switch
0 = water pressure switch
1 = water pressure transducer
2 = water pressure transducer (only pressure displayed)
0 .. 2 - 1 1
PAR 40 Modulating Pump Speed
-- = No modulation
AU = Automatic 30
.. 100
% 10 AU
PAR 41 ∆T Modulating pump delivery/Return 10 .. 40 % 1 20
PAR 47 System pump forcing (only in winter mode)
0 = Disabled
1 = Enabled
- - 0
RESET
PAR 48 INST Parameter set to default -- ; 1 - - -