2 Introduction
The LCD Annunciator for the 2008-9101, 2050-9101, and 2250-9101 panels provide remote annunciation of the fire alarm control unit
(FACU) status. The LCD display and LEDs indicate the visual status. The piezo sounder provides audible annunciation. You can enable or
lock access to the Annunciator switch functions using the keyswitch, see Accessing the user interface.
You can install a maximum number of four annunciators on the 2008-9101 FACU and a maximum number of eight annunciators on the
2050-9101 and 2250-9101 FACUs.
Note: From this point on, both the 2050-9101 and the 2250-9101 FACUs are referred as 2250, unless stated otherwise.
2.1 Compatibility
The 2008 FACU needs to be at revision 1.07 and the 2250 FACU needs to be at revision 1.03 or higher to support the 2606-9101 LCD
Annunciator. The LCD Annunciator must be at revision 1.01 or greater when used with 2250 and 2008 FACUs.
2.2 Reference documents
Refer to the following documents for more information on how to program and use the remote Annunciator.
Table 1: Document reference guide
Document
number
Title
579-1401 2008 Foundation Series Fire Alarm Control Unit Operation Guide
579-1409 2004 and 2008 Foundation Series Fire Alarm Control Units PC Programmer Installation Guide and Programming
Instructions
579-1404 2050 and 2250 Foundation Series Fire Alarm Control Units Installation Guide
579-1405 2050 and 2250 Foundation Series Fire Alarm Control Unit Operation Guide
579-1421 2050 and 2250 Foundation Series Fire Alarm Control Units PC Programmer Installation Guide and Programming
Instructions
page 4 579-1434 Rev B
Foundation Series 2606-9101 LCD Annunciator Installation Guide