4-1
Chapter 4
IDNAC Power Supply
Introduction An IDNAC power supply is used in the 4007ES (non Hybrid) panel. It provides 4 A and can
support:
• Addressable notification devices
• Addressable initiating devices
Refer to Figure 4-1 and Table 4-1 for the main components of the IDNAC power supply.
Figure 4-1. IDNAC Power Supply
Table 4-1. Main Components Information
P1 RUI Class A/B jumpers P2 IDNet Class A/B jumper
TB4 Battery connection TB2 IDNAC
P10 AC Power Connection TB3 Aux Relay 1 and 2
J15
DCAI
Zone/Relay Connection
J10 IDNet Loop 2
J7 Zone/Relay J11 IDNet Loop 3
J16 CPU Connection P5 Battery Depleted Jumper
J17 Option Connection P8 1-2 (default) / IDNet card on line
P11 City Circuit Connection
P9
25V Regulator Jumpers 1-2, 3-4
default. Power is fed to the zone/relay
card. No jumpers. Using 4007-9802,
25V Regulator Module
TB1
IDNet Loop 1, Aux
Power, RUI Connection
B
B
A
A
P2
2
1
B
B
A
A
P1
2
1
P2
IDNAC
AUX RELAY 1 AUX RELAY 2
LEDs
P4
5A Fuse
250VAC
BAT- BAT+
City/
Relay
Option
25V
REG
CPU
P5
TB4
P1
AUX PWR/
SNAC
IDNet
RUI
TB3
TB1
IDNet
Loop B
IDNet
Loop C
TB2
Zone/
Relay
J7
P5
J15
P9
J16
P8
P11
J17
P5
In this Chapter
Power Supply Specifications ................ 4-2 IDNAC Section Overview .................... 4-3
Specifications........................................ 4-3 Wiring....................................................4-3
Compatible Devices and Appliances .... 4-6 Auxiliary Relays Section Overview...... 4-8
Troubleshooting .................................... 4-9 SLC Channel Trouble LED Codes........ 4-9