5-6
Chapter 5 4007ES Power Supplies
Auxiliary Power Section, Continued
AUX PWR/SNAC
Overview
Output of AUX or NAC is 24V nominal. Minimum voltage is 19.5 @ minimum battery;
maximum is 29.5V. Aux Loads include the compatible 4007ES Annunciators series, 4090
series of IDNet ZAMs and IAMs and any listed device operating within the output limits of the
AUX. Calculate wiring loss for actual devices used. Compatible Appliances include 4904
series of free-run strobes, 4901 series non-smartsync horns, 4098 series TrueAlarm Sounder
Base and 4009 NAC extenders, used in reverse-polarity activation mode.
Table 5-5. Compatible Devices with 24V Aux. Power
2088-series relays 2098-series four-wire smoke detectors
4098-series four-wire smoke detectors 4190-9050/9051 4-20mA ZAMs
4090-series IDNet ZAMs
4100-7401, -7402 Graphic Annunciator
Modules
4602-6001, 4602-7001, 4602-7101, and
4602-9150 RCU/SCU Modules