Simplex 4010ES Series - Class B Monitor Zone Wiring; Class B Wiring

Simplex 4010ES Series
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specific Guidelines for Wiring a Waterflow Switch to a Class A Zone Module
Circuit is supervised. Supervisory power is 7.3 mA @ 24 VDC.
Rating:
- 20.4 to 32.0 VDC
- 60 mA @ 24 VDC
Connect N/O waterflow contact as shown in the figure. Connect to any zone on
the module.
Figure 19: Class A Monitor
Zone – Waterflow Switch Wiring
Class B Monitor Zone Wiring
Class B Wiring
This section shows typical wiring for a Class B monitor or security device circuit. Fire and security devices connect in the same manner to the following
monitor zone modules.
4100-5001 8 Zone Class B – Connects Fire Initiating Devices Only
4100-5004 8 Zone Class B – Connects either Fire Initiating Devices or Security Devices
4100-5005 8 Zone Class B – Connects either Fire Initiating Devices or Security Devices
4010-9920 8 Zone Class B – Connects Fire Initiating Devices Only
For information on wiring a waterflow switch to a class B monitor zone module, refer to the next section "Class B Waterflow Switch Wiring."
page 20 579-205 Rev. H
4010ES and 4100 4120-Series Class A/Class B Zone Modules Installation Instructions