page 5 579-1015 Rev U
4100ES Extended Power Supply Installation Instructions
Earth Connect Jumper
The EPS Earth Fault Enable/Disable jumper allows you to enable or disable Earth Fault detection.
• To enable the function: Place the jumper block on pins 1 and 2
• To disable the function: Place the jumper block on pins 2 and 3
Figure 6: Earth Connect Jumper Positions
Earth Fault detection is set to active on one EPS per battery location. A battery location is any cabinet connected to the master 4100 communications
channel without a TIC. A transponder cabinet is another battery location. Only ONE earth fault circuit should be active on all power supplies (EPS, TPS,
SPS, RPS) within a battery location. Disable earth fault detection on all other power supplies at a battery location. Any system that includes one or more
EPS MUST have earth detection from an EPS.
Battery Disconnect Jumper
Jumper P16 selects Low Battery operation.
• Jumper in Top position (pins 2-3) will cause panel shutdown when batteries are depleted.
• Jumper in Bottom position (pins 1-2) will allow panel to continue operating.
For S527 compliance, jumper must be installed to top position of P16.
Note: When jumper is set to pins 2-3, the EPS will not power-up from the battery.
Figure 7: Battery Disconnect Jumper Positions