4100ES Extended Power Supply Installation Instructions
Earth Connect Jumper
The EPS Earth Fault Enable/Disable jumper allows you to enable or disable Earth Fault detection.
To enable the function: Place the jumper block on pins 1 and 2
To disable the function: Place the jumper block on pins 2 and 3
Figure 6: Earth Connect Jumper Positions
Earth Fault detection is set to active on one EPS per battery location. A battery location is any cabinet connected to the master 4100 communications
channel without a TIC. A transponder cabinet is another battery location. Only ONE earth fault circuit should be active on all power supplies (EPS, TPS,
SPS, RPS) within a battery location. Disable earth fault detection on all other power supplies at a battery location. Any system that includes one or more
EPS MUST have earth detection from an EPS.
Battery Disconnect Jumper
Jumper P16 selects Low Battery operation.
Jumper in Top position (pins 2-3) will cause panel shutdown when batteries are depleted.
Jumper in Bottom position (pins 1-2) will allow panel to continue operating.
For S527 compliance, jumper must be installed to top position of P16.
Note: When jumper is set to pins 2-3, the EPS will not power-up from the battery.