11 Troubleshooting
SMA Solar Technology AG
Operating manual EVCxx-10-BE-en-10 49
Event number Message, cause and corrective measures
6501
Self-diagnosis > The internal temperature exceeds a permissible maxi-
mum value
The product has switched off because the internal temperature is above the
maximum permissible value.
Corrective measures:
Wait until the product has cooled down.
If this message is displayed frequently, contact the Service.
6630
Self-diagnosis > Fast-stop triggered
An overcurrent has been detected at the connection point. This triggered a fast
stop.
7001
The temperature sensor for the indoor temperature is defective.
The measurement is permanently outside the measuring range limits.
Corrective measures:
Contact the service.
7312
Update completed
7320
The device with serial number [xx] was successfully updated to
firmware version [xxx].
The firmware update was completed successfully.
7321
The device could not be updated
The firmware update was not successful.
Corrective measures:
Retry update.
If this message is displayed again, contact the Service.
7329
Condition test successful
The testing of the update conditions was successful. The firmware update
package is suitable for this product.