11 Operating Data and Parameters
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-58124
Name Description Value/range Explanation Default
value
Q-VArMod** Mode for reactive power
control
Off Sets reactive power to 0kVAr
and displacement power factor
cosφ to1
Off
VArCtlCom Specifies reactive power via ex-
ternal control unit, such as the
PowerReducerBox
PFCtlCom Specifies the displacement power
factor cosφ and the excitation of
the displacement power factor
via an external control unit such
as the PowerReducerBox
VArCnst Specifies reactive power in kVAr
via the parameter Q-VAr
VArCnstNom Specifies reactive power in% via
the parameter Q-VArNom
VArCnstNomAnIn The reactive power setpoint is im-
ported via an analog input.
PFCnst Manual specification of the dis-
placement power factor cosφ
and excitation of the displace-
ment power factor via the param-
eters PF-PF and PF-PFExt.
PFCnstAnIn Specifies the displacement power
factor cosφ at the analog input
QExlSpnt via control unit
PFCtlW Specifies the displacement power
factor cosφ depending on the
feed-in power
VArCtlVol Specifies reactive power as a
function of the grid voltage
VArCtlVolHystDb Specifies reactive power as a
function of the grid voltage (Q =
f(V) characteristic curve)
VArCtlVolHysDbA Specifies reactive power as a
function of the grid voltage with
activation power (for Italy)