HAT700 SERIES ATS CONTROLLER USER MANUAL
HAT700 Series ATS Controller 2018-12-13 Version 1.5 Page 50 of 51
ASCO Series 230 RTS
Parameters Setting
Switch Type
PC Three-stage
Aux. Output 1
ATS Power L
Aux. Output 2
ATS Power N
Aux. Output 4
S1 Open Control
Aux. Output 6
Gen Start Output
NOTE: All above are application diagrams of HAT700 series ATS controllers. However, HAT700 and
HAT700B have no sample current input, please skip over the current part of the diagram.
NoteAuxiliary Output 6 is default set as Genset Start Output (Normally Open) and there is only
normally close contact in it. The controller also can control the genset start even if there is no power
supply. If DC Power is selected, Genset Start Output port can be set as other items.