HGM501 Genset Controller User Manual Page 14 of 17
multifunctional window will start flashing: use and to select temperature
sensor type (there are six choices: L-0,L-1,L-2,L-3,L-4. L-5. L-0 stands for 'no
temperature sensor used'). Every time you press the button, the temperature sensor type
will change; when the needed type is displayed, press button to confirm and
automatically enter the next setting;
8) Generator temperature sensor type setting: the same as 7.
9) High temperature shutdown limit setting: engine temperature indicator illuminates,
multifunctional window first digit will start flashing, use and to choose a
value from 0 to 9 and to confirm; multifunctional window second digit will start
flashing, use and to choose a value from 0 to 9 and to confirm;
multifunctional window third digit will start flashing, use and to choose a
value from 0 to 9 and to confirm and enter the next setting automatically; the range
of temperature setting is 1-600℃ and it is invalid when outside this range.
10) Turn the start key from ON to OFF position to finish configuration.
NOTE: during configuration use button to enter the next menu item and to return to the
previous.
CAUTION: Please change inner controller parameters (rated generator voltage, generator frequency etc.)
only in standby mode, otherwise in can lead to shutdown or other abnormal condition.