active and a remote start signal/mains failure
occurs the HGM6110/20K will not give a start
command to the generator. If this input signal is
then removed, the HGM6110/20K will operate
as if a remote start/mains failure has occurred,
starting and loading the generator. This
function can be used to give an ‘AND’ function
so that a generator will only be called to start if
the mains fails and another condition exists
which requires the generator to run. If the
„Auto start Inhibit‟ signals become active once
more it will be ignored until the module has
returned the mains supply on load and
shutdown.