EasyManuals Logo

Smartgen HGM6120CAN User Manual

Default Icon
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
HGM6100N Series Genset Controller User Manual Page 22 of 47
No.
Items
Range
Default
Description
50(45)
Delay
(0-20.0)s
2.0
51(46)
Aux. Input 3
(0-25)
10
Factory default: Remote start input. See table
9.
52(47)
Active Type
(0-1)
0
Factory default: close.
53(48)
Delay
(0-20.0)s
2.0
54(49)
Aux. Input 4
(0-25)
11
Factory default: Low fuel level warn. See table
9.
55(50)
Active Type
(0-1)
0
Factory default: close.
56(51)
Delay
(0-20.0)s
2.0
57(52)
Aux. Input 5
(0-25)
12
Factory default: Low coolant level warn. See
table 9.
58(53)
Active Type
(0-1)
0
Factory default: close.
59(54)
Delay
(0-20.0)s
2.0
60(55)
Power On Mode
(0-2)
0
0: Stop Mode; 1: Manual Mode; 2: Auto Mode
61(56)
Module Address
(1-254)
1
The communication address of controller.
62(57)
Password
(0-9999)
0318
See NOTE4.
63(58)
Crank Disconnect
Condition
(0-6)
2
Conditions of disconnecting starter
(generator, magnetic pickup sensor, oil
pressure), each condition can be used alone
and simultaneously to separating the starter
motor and genset as soon as possible.
64(59)
Engine Speed of
Crank Disconnect
(0-3000)r/min
360
When engine speed is over this point, starter
will disconnect.
65(60)
Frequency of Crank
Disconnect
(0.0-30.0)Hz
14.0
When generator frequency is over this point,
starter will disconnect.
66(61)
Oil Pressure of Crank
Disconnect
(0-400)kPa
200
When engine oil pressure is over this point,
starter will disconnect.
67(62)
High Temp. Stop
Inhibit
(0-1)
0
Default: when temperature is overheat, the
genset alarm and shutdown. NOTE2
68(63)
Low OP Inhibit Stop
Inhibit
(0-1)
0
Default: when oil pressure is too low, it sends
alarm and shutdown. NOTE3
69(64)
AC System
(0-3)
0
0: 3P4W 1: 2P3W
2: 1P2W 3: 3P3W
70(65)
Temp. Sensor
Curve Type
(0-14)
8
SGX. See table 10.
71(66)
Pressure Sensor
Curve Type
(0-14)
8
SGX. See table 10.
72(67)
Fuel Level Sensor
Curve Type
(0-7)
3
SGD. See table 10.
73(68)
Generator Poles
(2-64)
4
Number of magnetic poles, used for
calculating rotating speed of generator
without speed sensor.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartgen HGM6120CAN and is the answer not in the manual?

Smartgen HGM6120CAN Specifications

General IconGeneral
BrandSmartgen
ModelHGM6120CAN
CategoryController
LanguageEnglish

Related product manuals