HGM6100N Series Genset Controller User Manual Page 22 of 47
Factory default: Remote start input. See table
9.
Factory default: Low fuel level warn. See table
9.
Factory default: Low coolant level warn. See
table 9.
0: Stop Mode; 1: Manual Mode; 2: Auto Mode
The communication address of controller.
Crank Disconnect
Condition
Conditions of disconnecting starter
(generator, magnetic pickup sensor, oil
pressure), each condition can be used alone
and simultaneously to separating the starter
motor and genset as soon as possible.
Engine Speed of
Crank Disconnect
When engine speed is over this point, starter
will disconnect.
Frequency of Crank
Disconnect
When generator frequency is over this point,
starter will disconnect.
Oil Pressure of Crank
Disconnect
When engine oil pressure is over this point,
starter will disconnect.
Default: when temperature is overheat, the
genset alarm and shutdown. NOTE2
Low OP Inhibit Stop
Inhibit
Default: when oil pressure is too low, it sends
alarm and shutdown. NOTE3
0: 3P4W 1: 2P3W
2: 1P2W 3: 3P3W
Pressure Sensor
Curve Type
Fuel Level Sensor
Curve Type
Number of magnetic poles, used for
calculating rotating speed of generator
without speed sensor.