Programming Instructions for SRU Boards
May 9, 2019 ©2019 Smartrise Engineering, Inc. All Rights Reserved Page 19
NOTE: Verify the POWER and RUN LEDs on the programming pod itself are off before
disconnecting the pod from the controller.
Move the programming pod from port J21 to J22, then click on the J22 check box and
begin programming. See Figure 21.
When programming is completed, cycle the power.
WARNING: ** DO NOT PRESS THE RESET BUTTON **
When the controller is fully powered and finished loading, verify that the controller is
programmed correctly by going to the MAIN MENU | ABOUT screen. Is all the
information correct?
a. If all the information is correct, the CT/COP Controller has been successfully
programmed. See Figure 22.
b. If the information is not correct, go to step 1.
Instructions*for*P rogrammin g*a*Group*Co ntroller*for*Non -Sim plex*Jobs*
Group controller software is located in the Controller Software folder.
Figure 23: Controller Software Folder
The folder is clearly labeled Group Software.
A controller cannot be programmed without power applied. Ensure that 24 VDC is applied to
the controller.
The following procedure describes how to program a group controller for non-simplex jobs.
Activate Dip Switch #1 on the group controller. (The group controller will not fault like
the MR controller.)