No.PF※※-OMZ0002
Flow Setting (set value only) of OUT1 · OUT2 [3 step setting mode]
3 step setting mode
In this mode, only the set values can be input, in just 3 steps.
Use this mode if the product is to be used straight away, after changing only the set values.
Default settings
When the flow exceeds the set value [P_1], the switch will be turned ON.
When the flow falls below the set value by the amount of hysteresis [H_1] or more, the switch will turn OFF.
If the operation shown in the diagram below is acceptable, then keep these settings.
PF2MC7501
Item
Default settings
[P_1] Set value of OUT1
250 L/min
[H_1] Hysteresis of OUT1
25 L/min
[P_2] Set value of OUT2
250 L/min
[H_2] Hysteresis of OUT2
25 L/min
PF2MC7102
Item
Default settings
[P_1] Set value of OUT1
500 L/min
[H_1] Hysteresis of OUT1
50 L/min
[P_2] Set value of OUT2
500 L/min
[H_2] Hysteresis of OUT2
50 L/min
PF2MC7202
Item
Default settings
[P_1] Set value of OUT1
1000 L/min
[H_1] Hysteresis of OUT1
100 L/min
[P_2] Set value of OUT2
1000 L/min
[H_2] Hysteresis of OUT2
100 L/min
: Only available for models with switch outputs for both OUT1 and OUT2.
: For input of hysteresis, perform the settings referring to [F 1] Setting of OUT1 (page 39 to) and [F 2] Setting of OUT2 (page 46 to).