-77-
No.PF※※-OMZ0002
Process data
Process data is the data which is exchanged periodically between the master and device.
This product process data consists of switch output status, error diagnostics, flow measurement value and
temperature measurement value.
(Refer to the table below.)
Bit offset
Item
Notes
0
OUT1 output
0: OFF 1: ON
1
OUT2 output
0: OFF 1: ON
8
Flow diagnosis
0: Within range 1: Out of range (HHH/LLL).
9
Fixed output
0: Normal output 1: Fixed output (for checking output)
15
Error diagnosis
0: Error is not generated 1: Error is generated
16 to 31
Flow measurement value
With sign: 16 bit
Bit offset
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Item
Flow measurement value (PD)
Bit offset
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Item
Error
Diagnosis
Fixed
output
Reservation
Flow
Diagnosis
Reservation
OUT2
OUT1
Switch output
The process data of this product is Big-Endian type.
When the transmission method of the upper communication is Little-Endian, the byte order will be
changed.
Refer to the table below for the Endian type of the major upper communication.
Endian type
Upper communication protocol
Big-Endian type
Such as PROFIBUS and PROFINET
Little-Endian type
Such as EtherNET/IP, EtherCAT and CC-Link IE Field.