-89-
No.PS※※-OMV0006-D
Specifications
Product No.
ZSE20B-L
(Vacuum pressure)
ZSE20BF-L
(Compound pressure)
ISE20B-L
(Positive pressure)
Applicable fluid Air, non-corrosive gas and non-flammable gas
Pressure
spec.
Rated pressure range
0.0 to -101.0 kPa
-100.0 to 100.0 kPa
-0.100 to 1.000 MPa
Display/Set pressure range
10.0 to -105.0 kPa
-105.0 to 105.0 kPa
-0.105 to 1.050 MPa
Display/Min. setting unit
0.1 kPa
0.001 MPa
Proof pressure
500 kPa
1.5 MPa
Power supply
spec.
Power supply
voltage
Used as switch output device 12 to 24 VDC (±10%), ripple max. 10%
Used as IO-Link device 18 to 30 VDC, ripple max.10% (p-p)
Current consumption 35 mA or less
Protection Polarity protection
A
ccuracy
Display accuracy
±
2%F.S.
±
1 digit (at ambient temperature 25
±
3
o
C)
Repeatability ±0.2%F.S. ±1 digit
Temperature characteristics
±
2%F.S. (25
o
C standard)
Switch outp
ut (During SIO mode)
Output type
Select from NPN or PNP open collector output
Output mode
Hysteresis mode, window comparator mode, error output,
switch output off
Switch operation Normal output, reversed output
Maximum load current
80 mA
Maximum applied voltage
30 V (during NPN output)
Internal voltage drop
(Residual voltage)
1.5 V or less (Load current 80 mA)
Delay time
1
1.5 ms or less, Variable at 0 to 60 s/0.01 s step
Hysteresis
Hysteresis mode
Variable from 0
2
Window comparator mode
Short circuit protection
Provided
Display
Unit
3
MPa, kPa, kgf/cm
2
, bar, psi, InHg, mmHg
MPa, kPa, kgf/cm
2
,
bar, psi
Display type
LCD
Number of displays
3-screen display (Main display, sub display x 2)
Display color
1) Main display: Red/Green
2) Sub display: Orange
Number of display digits
Main display: 4 digit (7-segments)
Sub display: 4 digit (Upper 1 digit 11-segments, 7-segments for other)
Operation light
LED is ON when switch output is ON (OUT1, OUT2: Orange)
Digital filter
4
Variable at 0 to 30 s/0.01 s step