9.1.2. Metering and sensing detail
Network type
1P 2 P 3P+ 3P+N
Source
1
1 phase
2 wire
2 phase
2 wire
3 phase
3 wire
3 phase
4 wire
Source
2
Source
1
1
N
1
2
1
3
2
1
N
Source
2
1
N
1
2
1
3
2
1
N
Voltage sensing
Source
1
-
V1
U12
-
U12, U23, U31
-
U12, U23, U31
V1, V2, V3
Source
2
-
V1
U12
-
U12, U23, U31
-
U12, U23, U31
V1, V2, V3
Source presence
(source available)
Source in ranges
(U,V,F)
Rotation phase
order
- - -
CAUTION ! In 3 phase networks with neutral; in balanced networks; there is a risk that loss of neutral will not be
detected. To limit this risk the reduce the source 1 and source 2 overvoltage and undervoltage thresholds.
(Cf chapter "12. Programming", page 27).
CAUTION ! When using 3P network without neutral, the controller must be powered using 184-300 VAC
between L1 and N. User may use a transformer between two phases to create this voltage.